| Option part number |
Feature code |
Description |
Power cord description |
Power source |
| |
| DPI 100-127V NEMA PDU |
| 39Y8905 |
5900 |
DPI 100-127V NEMA PDU |
attached line cord: 9ft NEMA L5-15P |
single-phase 15A/100-127V 60Hz |
| |
Specifications |
|
| Outlets: |
six NEMA 5-15R |
| Power Capacity: |
1440W @ 120V |
| Power Limit per Outlet: |
10A |
| Power Limit per PDU: |
12A circuit breaker |
| Power Monitoring: |
No |
| |
| |
| DPI Universal Rack PDU |
| |
5950 |
DPI Universal Rack PDU (US) |
rack power cable: 2m C19/C20 |
another PDU or UPS (100-250V) |
| 39Y8951 |
5949 |
line cord: 4.3m NEMA L5-20P |
single-phase 20A/120V 60Hz |
| |
5951 |
line cord: 4.3m NEMA L6-20P |
single-phase 20A/208V 60Hz |
| |
Specifications |
|
| Version: |
to PDU or UPS |
LV line cord |
HV line cord |
| Outlets: |
seven IEC C13 |
seven IEC C13 |
seven IEC C13 |
| Power Capacity: |
3000W @ 200V |
1800W @ 120V |
3120W @ 208V |
| Power Limit per Outlet: |
10A |
10A |
10A |
| Power Limit per PDU: |
15A circuit breaker |
15A circuit breaker |
15A circuit breaker |
| Power Monitoring: |
No |
No |
No |
| |
| |
| DPI Front-end PDU |
| 39Y8938 |
6002 |
DPI Single-phase 30A/120V Front-end PDU (US) |
detachable line cord: 2.5m NEMA L5-30P |
single-phase 30A/120V |
| 39Y8939 |
6003 |
DPI Single-phase 30A/208V Front-end PDU(US) |
detachable line cord: 2.5m NEMA L6-30P |
single-phase 30A/208V |
| 39Y8940 |
6004 |
DPI Single-phase 60A/208V Front-end PDU(US) |
detachable line cord: 2.5m IEC 309 2P+G |
single-phase 60A/208V |
| |
Specifications |
|
| Version: |
30A/120V |
30A/208V |
60A/208V |
| Outlets: |
three IEC C19 |
three IEC C19 |
three IEC C19 |
| Power Capacity: |
2880W @ 120V |
4992W @ 208V |
9984W @ 208V |
| Power Limit per Outlet: |
16A |
16A |
16A |
| Power Limit per PDU: |
24A |
24A |
48A |
| Power Monitoring: |
No |
No |
No |
| |
| |
| DPI High Density PDU |
| 73P5847 |
6071 |
DPI Three-phase 60A/208V High Density PDU (US) |
attached line cord: 4.3m IEC 309 3P+G |
three-phase 60A/208V |
| |
Specifications |
|
| Outlets: |
twelve IEC C19 |
| Power Capacity: |
17285W @ 208V |
| Power Limit per Outlet: |
16A |
| Grouping: |
four per phase |
| Power Limit per Group: |
27.7A |
| Power Monitoring: |
No |
| Note: |
This table describes some of the IBM Distributed Power Interconnect products, a family of power distribution
units (PDUs). See the table DPI Enterprise Power Distribution Units for more options. When ordering PDUs as
separate options, use the Option Part Number. For integrated rack-based solutions, Feature Codes are used to
order the PDUs as features of the Rack Cabinet. Feature Codes are used with the eConfig Product and Solution
Configurator.
|