A four-digit feature code is used to specify a component that is configurable in the IBM configurators, the eBusiness Configurator (eConfig) and the IBM Web-based Hardware Configurator, used in US and Canada. Options that do not have feature codes cannot be integrated by IBM into a system using these IBM configurators. To purchase options separately, refer to the option part number provided in this document.

DPI Power Distribution Units (Latin America)

The following PDU products have line cords included:

Option part number Description Power cord description Power source
 
DPI 100-127V NEMA PDU        
39Y8905 DPI 100-127V NEMA PDU attached line cord: 9ft NEMA L5-15P single-phase 15A/100-127V 60Hz
  Specifications  
Outlets: six NEMA 5-15R
Power Capacity: 1440W @ 120V
Power Limit per Outlet: 10A
Power Limit per PDU: 12A circuit breaker
Power Monitoring: No
 
DPI Universal Rack PDU        
any of the following: DPI Universal Rack PDU module without line cord rack power cable: 2m C19/C20 another PDU or UPS (100-250V)
39Y8962 DPI Universal Rack PDU (Argentina) line cord: 4.3m IRAM 2073 single-phase 16A/220V
39Y8960 DPI Universal Rack PDU (Brazil) line cord: 4.3m NBR 6147 single-phase 15A/125V
39Y8955 DPI Universal Rack PDU (Italy) line cord: 4.3m CEI 23-16 single-phase 16A/230V
39Y8951 DPI Universal Rack PDU (US) line cord: 4.3m NEMA L5-20P single-phase 20A/120V 60Hz
line cord: 4.3m NEMA L6-20P single-phase 20A/208V 60Hz
39Y8958 DPI Universal Rack PDU (Australia/New Zealand) line cord: 4.3m AS/NZS 3112 single-phase 15A/230V
39Y8959 DPI Universal Rack PDU (China) line cord: 4.3m GB 2099.1 single-phase 16A/220V
39Y8961 DPI Universal Rack PDU (India) line cord: 4.3m IS 6538 single-phase 16A/240V
40K9617 DPI Single-phase 32A/230V C13 Enterprise PDU (Aus/NZ) line cord: 4.3m AS/NZS 3112 single-phase 32A/220-240V
00D7593 DPI Universal Rack PDU (Japan LV) line cord: 4.3m JIS C-8303 single-phase 15A/100V
00D7594 DPI Universal Rack PDU (Japan HV) line cord: 4.3m JIS C-8303 single-phase 15A/200V
00D7595 DPI Universal Rack PDU (S Korea) line cord: 4.3m KSC 8305 single-phase 15A/250V
00D7596 DPI Universal Rack PDU (Taiwan LV) line cord: 4.3m CNS 10917-3 single-phase 16A/125V
00D7597 DPI Universal Rack PDU (Taiwan HV) line cord: 4.3m CNS 10917-3 single-phase 16A/250V
Specifications          
Version: to PDU or UPS Argentina Brazil (NEMA LV) (NEMA HV)
Outlets: seven IEC C13 seven IEC C13 seven IEC C13 seven IEC C13 seven IEC C13
Power Capacity: 3000W @ 200V 3300W @ 220V 1875W @ 125V 1800W @ 120V 3120W @ 208V
Power Limit per Outlet: 10A 10A 10A 10A 10A
Power Limit per PDU: 15A circuit breaker 15A circuit breaker 15A circuit breaker 13A 15A circuit breaker
Power Monitoring: No No No No No
DPI Front-end PDU        
39Y8938 DPI Single-phase 30A/120V Front-end PDU (US) line cord: 2.5m NEMA L5-30P single-phase 30A/120V
39Y8939 DPI Single-phase 30A/208V Front-end PDU (US) line cord: 2.5m NEMA L6-30P single-phase 30A/208V
39Y8940 DPI Single-phase 60A/208V Front-end PDU (US) line cord: 2.5m IEC 309 2P+G single-phase 60A/208V
39Y8934 DPI Single-phase 32A/230V Front-end PDU (non US) line cord: 2.5m IEC 309 P+N+G single-phase 32A/220-240V
39Y8937 DPI Single-phase 32A/230V Front-end PDU (Aus/NZ) line cord: 2.5m AS/NZS 3112 single-phase 32A/230V
39Y8936 DPI Single-phase 30A/220V Front-end PDU (S Korea) line cord: 2.5m KSC 8305 single-phase 30A/220V
Specifications          
Version: 30A/120V 30A/208V 60A/208V 32A/220-240V 63A/220-240V
Outlets: three IEC C19 three IEC C19 three IEC C19 three IEC C19 three IEC C19
Power Capacity: 2880W @ 120V 4992W @ 208V 9984W @ 208V 7360W @ 230V 14490W @ 230V
Power Limit per Outlet: 16A 16A 16A 16A 16A
Power Limit per PDU: 24A 24A 48A 32A 63A
Power Monitoring: No No No No No