Skip to main content


Rack power configurator


Attention
Attention:
A four-digit feature code is used to specify a component that is configurable in the IBM configurators, the eBusiness Configurator (eConfig) and the IBM Web-based Hardware Configurator, used in US and Canada. Options that do not have feature codes cannot be integrated by IBM into a system using these IBM configurators. To purchase options separately, refer to the option part number provided in this document.


DPI Power Distribution Units (Asia Pacific)

The following PDU products have line cords included:
Option part number Description Power cord description Power source
 
DPI 100-127V NEMA PDU
39Y8905 DPI 100-127V NEMA PDU attached line cord: 9ft NEMA L5-15P single-phase 15A/100-127V 60Hz
  Specifications  
Version: Taiwan (US LV)
Outlets: six NEMA 5-15R
Power Capacity: 1440W @ 120V
Power Limit per Outlet: 10A
Power Limit per PDU: 12A circuit breaker
Power Monitoring: No
 
 
DPI Universal Rack PDU
any of the following: DPI Universal Rack PDU module without line cord rack power cable: 2m C19/C20 another PDU or UPS (100-250V)
39Y8958 DPI Universal Rack PDU (Aus/NZ) line cord: 4.3m AS/NZ 3112 single-phase 15A/230V
39Y8959 DPI Universal Rack PDU (China) line cord: 4.3m GB 2099.1 single-phase 16A/220V
39Y8961 DPI Universal Rack PDU (India) line cord: 4.3m IS6538 single-phase 16A/240V
39Y8952 DPI Universal Rack PDU (Europe) line cord: 4.3m CEE7-VII single-phase 16A/230V
39Y8953 DPI Universal Rack PDU (Den/Sws) line cord: 4.3m IEC 309 P+N+G single-phase 16A/230V
39Y8956 DPI Universal Rack PDU (South Africa) line cord: 4.3m SABS 164 single-phase 16A/230V
39Y8957 DPI Universal Rack PDU (UK) line cord: 4.3m BS 1363/A single-phase 13A/230V
39Y8951 DPI Universal Rack PDU (US) line cord: 4.3m NEMA L5-20P single-phase 20A/120V 60Hz
line cord: 4.3m NEMA L6-20P single-phase 20A/208V 60Hz
Specifications
Version: to PDU or UPS Aus/NZ China Hong Kong (UK) Taiwan (US LV)
Outlets: seven IEC C13 seven IEC C13 seven IEC C13 seven IEC C13 seven IEC C13
Power Capacity: 3000W @ 200V 3450W @ 230V 3300W @ 220V 2990W @ 230V 1800W @ 120V
Power Limit per Outlet: 10A 10A 10A 10A 10A
Power Limit per PDU: 15A circuit breaker 15A circuit breaker 15A circuit breaker 13A 15A circuit breaker
Power Monitoring: No No No No No
 
 
DPI Front-end PDU
39Y8937 DPI Single-phase 32A/230V Front-end PDU (Aus/NZ) line cord: 2.5m AS/NZS 3112 single-phase 32A/230V
39Y8936 DPI Single-phase 30A/220V Fron-tend PDU (S Korea) line cord: 2.5m KSC 8305 single-phase 30A/220V
39Y8934 DPI Single-phase 32A/230V Front-end PDU (nonUS) line cord: 2.5m IEC 309 P+N+G single-phase 32A/220-240V
39Y8935 DPI Single-phase 63A/230V Front-end PDU (nonUS) line cord: 2.5m IEC 309 P+N+G single-phase 63A/220-240V
39Y8939 DPI Single-phase 30A/120V Front-end PDU (US) line cord: 2.5m NEMA L6-30P single-phase 30A/208V
39Y8940 DPI Single-phase 60A/208V Front-end PDU (US) line cord: 2.5m IEC 309 2P+G single-phase 60A/208V
39Y8938 DPI Single-phase 30A/120V Front-end PDU (US) line cord: 2.5m NEMA L5-30P single-phase 30A/120V
Specifications
Version: Aus/NZ S Korea 32A/220-240V 63A/220-240V 30A/120V
Outlets: three IEC C19 three IEC C19 three IEC C19 three IEC C19 three IEC C19
Power Capacity: 2880W @ 230V 7360W @ 220V 14490W @ 230V 7360W @ 230V 2880W @ 120V
Power Limit per Outlet: 16A 16A 16A 16A 16A
Power Limit per PDU: 32A 30A 63A 32A 24A
Power Monitoring: No No No No No
 
 
DPI High Density PDU
39Y8999 DPI Three-phase 32A/380-415V High Density PDU (nonUS) attached line cord: 4.3m IEC 309 3P+N+G three-phase wye 32A/380-415V
73P5847 DPI Three-phase 60A/208V High Density PDU (US) attached line cord: 4.3m IEC 309 3P+G three-phase delta 60A/208V
  Specifications  
Version: three-phase wye three-phase delta
Outlets: twelve IEC C19 twelve IEC C19
Power Capacity: 22080W @ 230V 17285W @ 208V
Power Limit per Outlet: 16A 16A
Grouping: four per phase four per phase
Power Limit per Group: 32A 27.7A
Power Monitoring: No No
 
Note: This table describes some of the IBM Distributed Power Interconnect products, a family of power distribution units (PDUs). See the table DPI Enterprise Power Distribution Units for more options.

Aug 26, 2008