Skip to main content
Skip to main content



Rack power configurator

Attention:
A four-digit feature code is used to specify a component that is configurable in the IBM configurators, the eBusiness Configurator (eConfig) and the IBM Web-based Hardware Configurator, used in US and Canada. Options that do not have feature codes cannot be integrated by IBM into a system using these IBM configurators. To purchase options separately, refer to the option part number provided in this document.

DPI Enterprise Power Distribution Units (Latin America)

NOTE: Also see the US/Canada section.

Order a PDU Module... Plus a Line Cord
Option part number PDU model description + Option part number Power cord description Power source
 
DPI Enterprise PDU and PDU+ (also see the DPI Enterprise PDU and PDU+ table for the US)                  
39Y8941 DPI C13 Enterprise Module (WW) + 40K9612 4.3m, 32A/230V, IEC 309 P+N+G (non-US) Line Cord single-phase 32A/220-240V
39Y8941 DPI C13 Enterprise Module (WW) + 40K9613 4.3m, 63A/230V, IEC 309 P+N+G (non-US) Line Cord single-phase 63A/220-240V
39Y8941 DPI C13 Enterprise Module (WW) + 40K9611 4.3m, 32A/380-415V, IEC 309 3P+N+G (non-US) Line Cord three-phase wye 32A/380-415V
39Y8941 DPI C13 Enterprise Module (WW) + 40K9618 DPI C13 Enterprise PDU (S Korea) Single-phase 30A/250V
  Specifications  
Version: 32A/220-240V 63A/220-240V 3-phase
Outlets: twelve IEC C13 twelve IEC C13 twelve IEC C13
Power Capacity: 7360W @ 230V 14490W @ 230V 22080W @ 230V
Power Limit per Outlet: 10A 10A 10A
Grouping: - - four per phase
Power Limit per Group: - - 32A
Power Limit per PDU: 32A 63A -
Power Monitoring: No No No
 
39Y8948 DPI C19 Enterprise Module (WW) + 40K9612 4.3m, 32A/230V, IEC 309 P+N+G (non-US) Line Cord single-phase 32A/220-240V
39Y8948 DPI C19 Enterprise Module (WW) + 40K9613 4.3m, 63A/230V, IEC 309 P+N+G (non-US) Line Cord single-phase 63A/220-240V
39Y8948 DPI C19 Enterprise Module (WW) + 40K9611 4.3m, 32A/380-415V, IEC 309 3P+N+G (non-US) Line Cord three-phase wye 32A/380-415V
  Specifications  
Version: 32A/220- 240V 63A/220-240V 3-phase
Outlets: six IEC C19 six IEC C19 six IEC C19
Power Capacity: 7360W @ 230V 14490W @ 230V 22080W @ 230V
Power Limit per Outlet: 16A 16A 16A
Grouping: - - two per phase
Power Limit per Group: - - 32A
Power Limit per PDU: 32A 63A -
Power Monitoring: No No No
 
39M2816 DPI C13 Enterprise PDU+Module (WW) + 40K9612 4.3m, 32A/230V, IEC 309 P+N+G (non-US) Line Cord single-phase 32A/220-240V
39M2816 DPI C13 Enterprise PDU+Module (WW) + 40K9613 4.3m, 63A/230V, IEC 309 P+N+G (non-US) Line Cord single-phase 63A/220-240V
39M2816 DPI C13 Enterprise PDU+Module (WW) + 40K9611 4.3m, 32A/380-415V, IEC 309 3P+N+G (non-US) Line Cord three-phase wye 32A/380-415V
  Specifications  
Version: 32A/220- 240V 63A/220-240V 3-phase
Outlets: twelve IEC C13 twelve IEC C13 twelve IEC C13
Power Capacity: 7360W @ 230V 14490W @ 230V 22080W @ 230V
Power Limit per Outlet: 10A 10A 10A
Grouping: - - four per phase
Power Limit per Group: - - 32A
Power Limit per PDU: 32A 63A -
Power Monitoring: Yes Yes Yes
 

Note:

This table describes some of the IBM Distributed Power Interconnect products, a family of power distribution units (PDUs). See the table DPI Enterprise Power Distribution Units for more options.



         May 14, 2012