Rack power configurator
| A four-digit feature code is used to specify a component that is configurable in the IBM configurators, the eBusiness Configurator (eConfig) and the IBM Web-based Hardware Configurator, used in US and Canada. Options that do not have feature codes cannot be integrated by IBM into a system using these IBM configurators. To purchase options separately, refer to the option part number provided in this document. |
Tab navigation
- Overview
- US & Canada
- EMEA- selected tab,
- Asia Pacific
- Latin America
DPI Enterprise Power Distribution Units (EMEA)
| Order a PDU Module... | Plus a Line Cord | |||||||
| Option part number | PDU model description | + | Option part number | Power cord description | Power source | |||
|---|---|---|---|---|---|---|---|---|
| DPI Enterprise PDU and PDU+ | ||||||||
| 39Y8941 | DPI C13 Enterprise Module (WW) | + | 40K9612 | 4.3m, 32A/230V, IEC 309 P+N+G (non-US) Line Cord | single-phase 32A/220-240V | |||
| 39Y8941 | DPI C13 Enterprise Module (WW) | + | 40K9613 | 4.3m, 63A/230V, IEC 309 P+N+G (non-US) Line Cord | single-phase 63A/220-240V | |||
| 39Y8941 | DPI C13 Enterprise Module (WW) | + | 40K9611 | 4.3m, 32A/380-415V, IEC 309 3P+N+G (non-US) Line Cord | three-phase wye 32A/380-415V | |||
| 39Y8941 | DPI C13 Enterprise Module (WW) | + | 40K9615 | DPI C13 Enterprise PDU (US) | Single-phase 60A/208V | |||
| 39Y8941 | DPI C13 Enterprise Module (WW) | + | 40K9617 | DPI C13 Enterprise PDU (Aus/NZ) | Single-phase 32A/230V | |||
| 39Y8941 | DPI C13 Enterprise Module (WW) | + | 40K9618 | DPI C13 Enterprise PDU (S Korea) | Single-phase 30A/250V | |||
| Specifications | ||||||||
| Version: | 32A/220-240V | 63A/220-240V | 3-phase | |||||
| Outlets: | twelve IEC C13 | twelve IEC C13 | twelve IEC C13 | |||||
| Power Capacity: | 7360W @ 230V | 14490W @ 230V | 22080W @ 230V | |||||
| Power Limit per Outlet: | 10A | 10A | 10A | |||||
| Grouping: | - | - | four per phase | |||||
| Power Limit per Group: | - | - | 32A | |||||
| Power Limit per PDU: | 32A | 63A | - | |||||
| Power Monitoring: | No | No | No | |||||
| 39Y8948 | DPI C19 Enterprise Module (WW) | + | 40K9612 | 4.3m, 32A/230V, IEC 309 P+N+G (non-US) Line Cord | single-phase 32A/220-240V | |||
| 39Y8948 | DPI C19 Enterprise Module (WW) | + | 40K9613 | 4.3m, 63A/230V, IEC 309 P+N+G (non-US) Line Cord | single-phase 63A/220-240V | |||
| 39Y8948 | DPI C19 Enterprise Module (WW) | + | 40K9611 | 4.3m, 32A/380-415V, IEC 309 3P+N+G (non-US) Line Cord | three-phase wye 32A/380-415V | |||
| Specifications | ||||||||
| Version: | 32A/220-240V | 63A/220-240V | 3-phase | |||||
| Outlets: | six IEC C19 | six IEC C19 | six IEC C19 | |||||
| Power Capacity: | 7360W @ 230V | 14490W @ 230V | 22080W @ 230V | |||||
| Power Limit per Outlet: | 16A | 16A | 16A | |||||
| Grouping: | - | - | two per phase | |||||
| Power Limit per Group: | - | - | 32A | |||||
| Power Limit per PDU: | 32A | 63A | - | |||||
| Power Monitoring: | No | No | No | |||||
| 39M2816 | DPI C13 Enterprise PDU+Module (WW) | + | 40K9612 | 4.3m, 32A/230V, IEC 309 P+N+G (non-US) Line Cord | single-phase 32A/220-240V | |||
| 39M2816 | DPI C13 Enterprise PDU+Module (WW) | + | 40K9613 | 4.3m, 63A/230V, IEC 309 P+N+G (non-US) Line Cord | single-phase 63A/220-240V | |||
| 39M2816 | DPI C13 Enterprise PDU+Module (WW) | + | 40K9611 | 4.3m, 32A/380-415V, IEC 309 3P+N+G (non-US) Line Cord | three-phase wye 32A/380-415V | |||
| Specifications | ||||||||
| Version: | 32A/220-240V | 63A/220-240V | 3-phase | |||||
| Outlets: | twelve IEC C13 | twelve IEC C13 | twelve IEC C13 | |||||
| Power Capacity: | 7360W @ 230V | 14490W @ 230V | 22080W @ 230V | |||||
| Power Limit per Outlet: | 10A | 10A | 10A | |||||
| Grouping: | - | - | four per phase | |||||
| Power Limit per Group: | - | - | 32A | |||||
| Power Limit per PDU: | 32A | 63A | - | |||||
| Power Monitoring: | Yes | Yes | Yes | |||||
Note:
This table describes some of the IBM Distributed Power Interconnect products, a family of power distribution