| A four-digit feature code is used to specify a component that is configurable in the IBM configurators, the eBusiness Configurator (eConfig) and the IBM Web-based Hardware Configurator, used in US and Canada. Options that do not have feature codes cannot be integrated by IBM into a system using these IBM configurators. To purchase options separately, refer to the option part number provided in this document. |
UPS runtime estimator
Steps to determine UPS runtimes and suitable UPS for desired
configurations:
IBM UPS 750T, 1000T, 1500T
| Tower | ||||
| Low Voltage Versions (US) | UPS750TLV | UPS1000TLV | UPS1500TLV | |
| New T-M-F Ordering System4 | 2130TU1-1081 | 2130TU1-1083 | 2130TU1-1085 | |
| Part Number | 2130R1X | 2130R3X | 2130R5X | |
| (Old Part Number) | (21301TX) | (21303TX) | (21305TX) | |
| Low Voltage Versions (Int'l) | UPS750THV | UPS1000THV | UPS1500THV | |
| Part Number | 2130R2X | 2130R4X | 2130R6X | |
| (Old Part Number) | (21302TX) | (21304TX) | (21306TX) | |
| Japan Versions | UPS750TJV | UPS1000TJV | UPS1500TJV | |
| Part Number | 2130R7X | 2130R8X | 2130R9X | |
| (Old Part Number) | (21307TX) | (21308TX) | (21309TX) | |
UPS attributes |
||||
Communications links to servers |
Serial/USB/Enet |
Serial/USB/Enet |
Serial/USB/Enet |
|
Color |
black |
black |
black |
|
APC SmartSlot |
one |
one |
one |
|
International models |
||||
50 or 60Hz, single phase,VAC: |
220-240(xxx)1,2 |
220-240(xxx)1,2 |
220-240(xxx)1,2 |
|
10-Amp, IEC 320-C13 (Device)receptacles |
6 |
8 |
8 |
|
16-Amp, IEC 320-C19 (PDU)receptacles |
- |
- |
- |
|
Receptacles (NEMA L5-20R) |
- |
- |
- |
|
Line cord length, NEMA plug |
- |
- |
- |
|
Line cord receptacle (IEC 320-) |
C143 |
C143 |
C143 |
|
Low Voltage Versions (US models and Japan models) |
||||
50 or 60Hz, single phase,VAC: |
100-127(120)1 |
100-127(120)1 |
100-127(120)1 |
|
Receptacles (NEMA 5-15R) |
6 |
8 |
8 |
|
Receptacles (NEMA L5-20R) |
- |
- |
- |
|
10-Amp, IEC 320-C13 (Device)receptacles |
- |
- |
- |
|
16-Amp, IEC 320-C19 (PDU)receptacles |
- |
- |
- |
|
Line cord length, NEMA plug |
6ft, 5-15P |
6ft, 5-15P |
6ft, 5-15P |
|
Line cord receptacle (IEC 320-) |
- |
- |
- |
|
| Tower | |||
| UPS750T | UPS1000T | UPS1500T | |
| Total load (watts) | Runtime (minutes) | Runtime (minutes) | Runtime (minutes) |
| 50 | 105 | 224 | 269 |
| 100 | 57 | 127 | 157 |
| 200 | 28 | 64 | 80 |
| 300 | 18 | 41 | 51 |
| 400 | 13 | 29 | 37 |
| 500 | 10 | 23 | 28 |
| 600 | - | 18 | 22 |
| 700 | - | 15 | 18 |
| 800 | - | 12 | 15 |
| 900 | - | 11 | 13 |
| 1000 | - | 9 | 11 |
| 1200 | - | - | 9 |
| 1400 | - | - | 7 |
| Option number | Description |
| 39Y7930 | 2.8m, 10A/220V, C13 to IRAM 2073 (Argentina) Line Cord |
| 39Y7929 | 2.8m, 10A/125V, C13 to NBR 6147 (Brazil) Line Cord |
| 39Y7917 | 2.8m, 10A/230V, C13 to CEE7-VII (Europe) Line Cord |
| 39Y7918 | 2.8m, 10A/230V, C13 to DK2-5a (Denmark) Line Cord |
| 39Y7920 | 2.8m, 10A/230V, C13 to SI 32 (Israel) Line Cord |
| 39Y7921 | 2.8m, 10A/230V, C13 to CEI 23-16 (Italy) Line Cord |
| 39Y7922 | 2.8m, 10A/230V, C13 to SABS 164 (South Africa) Line Cord |
| 39Y7919 | 2.8m, 10A/230V, C13 to SEV 1011-S24507 (Sws) Line Cord |
| 39Y7923 | 2.8m, 10A/230V, C13 to BS 1363/A (UK) Line Cord |
| 39Y7924 | 2.8m, 10A/230V, C13 to AS/NZS 3112 (Aus/NZ) Line Cord |
| 39Y7927 | 2.8m, 10A/240V, C13 to IS6538 (India) Line Cord |
| 39Y7928 | 2.8m, 10A/220V, C13 to GB 2099.1 (China) Line Cord |
| 39Y7925 | 2.8m, 10A/220V, C13 to KSC 8305 (S. Korea) Line Cord |
IBM UPS3000LV and HV
| Tower or rack mount | ||||
| Version | UPS3000LV | UPS3000HV | UPS extend run battery pack | |
| New T-M-F Ordering System1 | 2130RU1-1077 | 2130RU1-1078 | FC 5742 | |
| Part Number | 21301RX | 21302RX | 40K9620 | |
UPS attributes |
||||
Communications links to servers |
Serial/USB/Enet |
Serial/USB/Enet |
- |
|
Color |
black |
black |
black |
|
EIA height |
2U |
2U |
2U |
|
Versions |
|
Low Voltage |
High Voltage |
|
50 or 60Hz, single phase,VAC: |
120(120)1 |
220-240(xxx)1, 2 |
- |
|
| Maximum power capacity (watts) | 2700 | 2700 | - | |
10-Amp, IEC 320-C13 (Device) receptacles |
- |
94 |
- |
|
16-Amp, IEC 320-C19 (PDU)receptacles |
- |
13 |
- |
|
Receptacles (NEMA 5-15R) |
6 |
- |
- |
|
Receptacles (NEMA L5-30R) |
1 |
- |
- |
|
Attached line cord length, NEMA plug type |
12ft, L5-30P |
- |
- |
|
Line cord receptacle(IEC 320-) |
- |
C205 |
- |
|
| Number of battery packs (P/N 40K9620) | |||||
| +0 | +1 | +2 | +3 | +4 | |
| Total Load (Watts) | Runtime ( hours / minutes) |
Runtime ( hours / minutes) |
Runtime ( hours / minutes) |
Runtime ( hours / minutes) |
Runtime ( hours / minutes) |
|---|---|---|---|---|---|
200 |
1/3 |
5/16 |
7/57 |
11/15 |
14/34 |
300 |
55 |
4/35 |
7/0 |
9/55 |
12/50 |
400 |
48 |
4/1 |
6/6 |
8/39 |
11/12 |
500 |
42 |
3/31 |
5/19 |
7/31 |
9/44 |
600 |
36 |
3/3 |
4/31 |
6/24 |
8/17 |
700 |
31 |
2/35 |
3/50 |
5/26 |
7/2 |
800 |
26 |
2/12 |
3/20 |
4/43 |
6/6 |
900 |
23 |
1/55 |
2/51 |
4/2 |
5/14 |
1000 |
19 |
1/38 |
2/23 |
3/23 |
4/23 |
1100 |
16 |
1/22 |
2/4 |
2/56 |
3/48 |
1200 |
14 |
1/11 |
1/48 |
2/33 |
3/19 |
1300 |
12 |
1/2 |
1/35 |
2/14 |
2/54 |
1400 |
10 |
54 |
1/20 |
1/54 |
2/28 |
1500 |
9 |
46 |
1/11 |
1/41 |
2/10 |
1600 |
8 |
41 |
1/8 |
1/37 |
2/5 |
1700 |
8 |
40 |
1/8 |
1/37 |
2/5 |
1800 |
8 |
40 |
1/8 |
1/37 |
2/5 |
1900 |
7 |
39 |
1/0 |
1/25 |
1/50 |
2000 |
7 |
35 |
1/0 |
1/25 |
1/50 |
2100 |
7 |
35 |
1/0 |
1/25 |
1/50 |
| Number of battery packs (P/N 40K9620) | |||||
| +0 | +1 | +2 | +3 | +4 | |
| Total Load (Watts) | Runtime ( hours / minutes) |
Runtime ( hours / minutes) |
Runtime ( hours / minutes) |
Runtime ( hours / minutes) |
Runtime ( hours / minutes) |
|---|---|---|---|---|---|
200 |
1/3 |
4/38 |
9/5 |
12/48 |
16/42 |
300 |
55 |
4/5 |
8/0 |
11/16 |
14/42 |
400 |
48 |
3/33 |
6/59 |
9/59 |
12/50 |
500 |
42 |
3/6 |
6/4 |
8/33 |
11/10 |
600 |
36 |
2/38 |
5/10 |
7/17 |
9/30 |
700 |
31 |
2/14 |
4/23 |
6/11 |
8/4 |
800 |
26 |
1/56 |
3/48 |
5/22 |
7/0 |
900 |
23 |
1/40 |
3/16 |
4/36 |
6/0 |
1000 |
19 |
1/23 |
2/44 |
3/51 |
5/2 |
1100 |
16 |
1/12 |
2/22 |
3/20 |
4/22 |
1200 |
14 |
1/3 |
2/4 |
2/54 |
3/48 |
1300 |
12 |
55 |
1/48 |
2/33 |
3/20 |
1400 |
10 |
47 |
1/32 |
2/10 |
2/50 |
1500 |
9 |
45 |
1/28 |
2/4 |
2/42 |
1600 |
9 |
41 |
1/20 |
1/53 |
2/28 |
1700 |
8 |
40 |
1/18 |
1/50 |
2/24 |
1800 |
8 |
40 |
1/18 |
1/50 |
2/24 |
1900 |
7 |
35 |
1/8 |
1/36 |
2/6 |
2000 |
7 |
35 |
1/8 |
1/36 |
2/6 |
2100 |
7 |
33 |
1/5 |
1/32 |
2/0 |
2200 |
6 |
30 |
58 |
1/22 |
1/48 |
2300 |
6 |
30 |
58 |
1/22 |
1/48 |
2400 |
6 |
30 |
58 |
1/22 |
1/48 |
2500 |
6 |
26 |
51 |
1/12 |
1/34 |
2600 |
5 |
25 |
49 |
1/9 |
1/30 |
2700 |
5 |
25 |
49 |
1/9 |
1/30 |
| Option number | Description |
| 40K9772 | 4.3m, 16A/208V, C19 to NEMA L6-20P (US) Line Cord |
| 40K9777 | 4.3m, 16A/220V, C19 to IRAM 2073 (Argentina) Line Cord |
| 40K9775 | 4.3m, 15A/125V, C19 to NBR 6147 (Brazil) Line Cord |
| 40K9766 | 4.3m, 16A/230V, C19 to CEE7-VII (Europe) Line Cord |
| 40K9769 | 4.3m, 16A/230V, C19 to IEC 309-P+N+G (Den/Sws) Line Cord |
| 40K9771 | 4.3m, 16A/230V, C19 to SI 32 (Israel) Line Cord |
| 40K9768 | 4.3m, 16A/230V, C19 to CEI 23-16 (Italy) Line Cord |
| 40K9770 | 4.3m, 16A/230V, C19 to SABS 164 (South Africa) Line Cord |
| 40K9767 | 4.3m, 13A/230V, C19 to BS 1363/A w/13A fuse (UK) Line Cord |
| 40K9773 | 4.3m, 15A/230V, C19 to AS/NZS 3112 (Aus/NZ) Line Cord |
| 40K9774 | 4.3m, 16A/220V, C19 to GB 2099.1 (China) Line Cord |
| 40K9776 | 4.3m, 16A/240V, C19 to IS 6538 (India) Line Cord |
IBM UPS 7500XHV, 10000XHV
| Tower or rack mount | |||||
|---|---|---|---|---|---|
| Version | UPS7500XHV | UPS10000XHV | UPS extend run battery pack | ||
| New T-M-F Ordering System6 | 2130RU1-1079 | 2130RU1-1080 | FC 5743 | ||
| Part number | 21303RX | 21304RX | 39Y8857 | ||
| (Old part number) | (21306RX) | (21308RX) | (25R5582) | ||
| UPS attributes | |||||
| Communication links to servers | Serial/USB/Enet | Serial/USB/Enet | -- | ||
| Color | black | black | black | ||
| EIA height | 6U | 6U | 3U | ||
| Versions | |||||
| 50 or 60Hz, single phase, VAC: | 220-240(xxx) 1, 2 | 220-240(xxx)1, 2 | - | ||
| Maximum power capacity (watts) | 6000 | 8000 | - | ||
| 10 Amp, IEC 320-C13 receptacles | - | - | - | ||
| 16 Amp, IEC 320-C19 receptacles | 43, 4 | 43, 4 | - | ||
| Line cord receptacle | terminal block5 | terminal block5 | - | ||
| Number of battery packs (P/N 39Y8857) | ||||
| +0 | +1 | +2 | +4 | |
| Watts load | Runtime (hours/ minutes) |
Runtime (hours/ minutes) |
Runtime (hours/ minutes) |
Runtime (hours/ minutes) |
| 200 | 4/6 | 7/36 | 11/54 | 20/54 |
| 300 | 3/6 | 5/48 | 9/6 | 16/0 |
| 400 | 2/30 | 4/36 | 7/18 | 12/48 |
| 500 | 2/6 | 3/54 | 6/6 | 10/42 |
| 600 | 1/48 | 3/18 | 5/12 | 9/12 |
| 700 | 1/30 | 2/54 | 4/30 | 8/0 |
| 800 | 1/18 | 2/30 | 4/0 | 7/0 |
| 900 | 1/12 | 2/18 | 3/36 | 6/12 |
| 1000 | 1/6 | 2/0 | 3/12 | 5/42 |
| 1200 | 55 | 1/42 | 2/42 | 4/48 |
| 1400 | 47 | 1/30 | 2/18 | 4/6 |
| 1600 | 41 | 1/12 | 2/0 | 3/36 |
| 1800 | 36 | 1/6 | 1/48 | 3/12 |
| 2000 | 32 | 1/0 | 1/36 | 2/54 |
| 3000 | 19 | 39 | 1/0 | 1/48 |
| 4000 | 13 | 28 | 46 | 1/18 |
| 5000 | 10 | 21 | 35 | 1/0 |
| 6000 | 7 | 16 | 28 | 52 |
| 7000 | 5 | 13 | 23 | 44 |
| 8000 | 4 | 11 | 20 | 37 |
| Note: UPS7500 is rated for up to 6000 total watts; UPS10000 is rated for up to 8000 total watts. | ||||
October 7, 2008
|
|