Appendix A. Uninterruptible power supplies
| A four-digit feature code is used to specify a component that is configurable in the IBM configurators, the eBusiness Configurator (eConfig) and the IBM Web-based Hardware Configurator, used in US and Canada. Options that do not have feature codes cannot be integrated by IBM into a system using these IBM configurators. To purchase options separately, refer to the option part number provided in this document. |
UPS runtime estimator
Steps to determine UPS runtimes and suitable UPS for desired
configurations:
- Using the 'Power Product Data' table in the 'Power Data
Overview Appendix', sum the power load (watts) of all devices
in the configuration. Use either Maximum Load for minimum
runtimes, or Typical Load for typical runtimes. - Using the 'Runtimes' table, locate the configuration's total
load calculated in step 1. - Select the most appropriate UPS model to achieve the desired
runtime.
Note:
If the configuration's total load is greater than the entries in the 'Runtimes' table, split the load across two or more UPS units.
IBM UPS 1000T, 1500T
| Tower | |||
|---|---|---|---|
| Low Voltage Versions (US) | UPS1000TLV | UPS1500TLV | |
| New T-M-F Ordering System4 | 2130TU1-1083 | 2130TU1-1085 | |
| Part Number | 2130R3X | 2130R5X | |
| (Old Part Number) | (21303TX*) | (21305TX*) | |
| Low Voltage Versions (Int'l) | UPS1000THV | UPS1500THV | |
| Part Number | 2130R4X | 2130R6X | |
| (Old Part Number) | (21304TX) | (21306TX) | |
| Japan Versions | UPS1000TJV | UPS1500TJV | |
| Part Number | 2130R8X | 2130R9X | |
| (Old Part Number) | (21308TX) | (21309TX) | |
|
UPS attributes |
|||
| Communications links to servers | Serial/USB/Enet | Serial/USB/Enet | |
| Color | black | black | |
| APC SmartSlot | one | one | |
|
International models |
|||
| 50 or 60Hz, single phase,VAC: | 220-240(xxx)1,2 | 220-240(xxx)1,2 | |
| 10-Amp, IEC 320-C13 (Device)receptacles | 8 | 8 | |
| 16-Amp, IEC 320-C19 (PDU)receptacles | - | - | |
| Receptacles (NEMA L5-20R) | - | - | |
| Line cord length, NEMA plug | - | - | |
| Line cord receptacle (IEC 320-) | C143 | C143 | |
|
Low Voltage Versions (US models and Japan models) |
|||
| 50 or 60Hz, single phase,VAC: | 100-127(120)1 | 100-127(120)1 | |
| Receptacles (NEMA 5-15R) | 8 | 8 | |
| Receptacles (NEMA L5-20R) | - | - | |
| 10-Amp, IEC 320-C13 (Device)receptacles | - | - | |
| 16-Amp, IEC 320-C19 (PDU)receptacles | - | - | |
| Line cord length, NEMA plug | 6ft, 5-15P | 6ft, 5-15P | |
| Line cord receptacle (IEC 320-) | - | - | |
Notes:
- How-to-Read example for 200-240(208): Input VAC is 200-240
as
is the UPS output when electric service is active. When electric
service is interrupted and the UPS is on battery, the UPS output
is 208 VAC. - Battery output may be set to 220, 225, 230 or 240 VAC.
- Country-specific line cords available as options.
- Type-Model-Feature ordering system now used in the US and Canada.
| Tower | ||
|---|---|---|
| UPS1000T | UPS1500T | |
| Total load (watts) | Runtime (minutes) | Runtime (minutes) |
| 50 | 224 | 269 |
| 100 | 127 | 157 |
| 200 | 64 | 80 |
| 300 | 41 | 51 |
| 400 | 29 | 37 |
| 500 | 23 | 28 |
| 600 | 18 | 22 |
| 700 | 15 | 18 |
| 800 | 12 | 15 |
| 900 | 11 | 13 |
| 1000 | 9 | 11 |
| 1200 | - | 9 |
| 1400 | - | 7 |
Note:
- Data provided by APC.
| Option number | Description |
|---|---|
| 39Y7930* | 2.8m, 10A/220V, C13 to IRAM 2073 (Argentina) Line Cord |
| 39Y7929* | 2.8m, 10A/125V, C13 to NBR 6147 (Brazil) Line Cord |
| 39Y7917* | 2.8m, 10A/230V, C13 to CEE7-VII (Europe) Line Cord |
| 39Y7918* | 2.8m, 10A/230V, C13 to DK2-5a (Denmark) Line Cord |
| 39Y7920* | 2.8m, 10A/230V, C13 to SI 32 (Israel) Line Cord |
| 39Y7921 | 2.8m, 10A/230V, C13 to CEI 23-16 (Italy) Line Cord |
| 39Y7922* | 2.8m, 10A/230V, C13 to SABS 164 (South Africa) Line Cord |
| 39Y7919* | 2.8m, 10A/230V, C13 to SEV 1011-S24507 (Sws) Line Cord |
| 39Y7923* | 2.8m, 10A/230V, C13 to BS 1363/A (UK) Line Cord |
| 39Y7924* | 2.8m, 10A/230V, C13 to AS/NZS 3112 (Aus/NZ) Line Cord |
| 39Y7927* | 2.8m, 10A/240V, C13 to IS6538 (India) Line Cord |
| 39Y7928* | 2.8m, 10A/220V, C13 to GB 2099.1 (China) Line Cord |
| 39Y7925* | 2.8m, 10A/220V, C13 to KSC 8305 (S. Korea) Line Cord |
* IBM has withdrawn this product from marketing.
IBM UPS3000LV* and HV*
| Tower or rack mount | ||||
|---|---|---|---|---|
| Version | UPS3000LV* | UPS3000HV* | UPS extend run battery pack | |
| New T-M-F Ordering System1 | 2130RU1-1077 | 2130RU1-1078 | FC 5742 | |
| Part Number | 21301RX* | 21302RX* | 40K9620* | |
|
UPS attributes |
||||
| Communications links to servers | Serial/USB/Enet | Serial/USB/Enet | - | |
| Color | black | black | black | |
| EIA height | 2U | 2U | 2U | |
|
Versions |
Low Voltage |
High Voltage |
||
| 50 or 60Hz, single phase,VAC: | 120(120)1 | 220-240(xxx)1, 2 | - | |
| Maximum power capacity (watts) | 2700 | 2700 | - | |
| 10-Amp, IEC 320-C13 (Device) receptacles | - | 94 | - | |
| 16-Amp, IEC 320-C19 (PDU)receptacles | - | 13 | - | |
| Receptacles (NEMA 5-15R) | 6 | - | - | |
| Receptacles (NEMA L5-30R) | 1 | - | - | |
| Attached line cord length, NEMA plug type | 12ft, L5-30P | - | - | |
| Line cord receptacle(IEC 320-) | - | C205 | - | |
* IBM has withdrawn this product from marketing.
Notes:
- How-to-Read example for 200-240(208): Input VAC is 200-240
as
is the UPS output when electric service is active. When electric
service is interrupted and the UPS is on battery, the UPS output
is 208 VAC. - Battery output may be set to 220, 225, 230 or 240 VAC.
- One 2.5m PDU jumper cable ships with the UPS for attachment
from the IEC 320-C19 receptacle to a Power Distribution Unit (PDU)
with C20 inlet. - Four IEC power cables are provided to attach devices to the
UPS outlets, which are 2m long with IEC 320-C13/C14 connectors. - Country-specific line cords are available as options.
- Type-Model-Feature ordering system now used in the US and Canada.
| Number of battery packs (P/N 40K9620) | |||||
|---|---|---|---|---|---|
| +0 | +1 | +2 | +3 | +4 | |
| Total Load (Watts) | Runtime ( hours / minutes) |
Runtime ( hours / minutes) |
Runtime ( hours / minutes) |
Runtime ( hours / minutes) |
Runtime ( hours / minutes) |
| 200 | 1/3 | 5/16 | 7/57 | 11/15 | 14/34 |
| 300 | 55 | 4/35 | 7/0 | 9/55 | 12/50 |
| 400 | 48 | 4/1 | 6/6 | 8/39 | 11/12 |
| 500 | 42 | 3/31 | 5/19 | 7/31 | 9/44 |
| 600 | 36 | 3/3 | 4/31 | 6/24 | 8/17 |
| 700 | 31 | 2/35 | 3/50 | 5/26 | 7/2 |
| 800 | 26 | 2/12 | 3/20 | 4/43 | 6/6 |
| 900 | 23 | 1/55 | 2/51 | 4/2 | 5/14 |
| 1000 | 19 | 1/38 | 2/23 | 3/23 | 4/23 |
| 1100 | 16 | 1/22 | 2/4 | 2/56 | 3/48 |
| 1200 | 14 | 1/11 | 1/48 | 2/33 | 3/19 |
| 1300 | 12 | 1/2 | 1/35 | 2/14 | 2/54 |
| 1400 | 10 | 54 | 1/20 | 1/54 | 2/28 |
| 1500 | 9 | 46 | 1/11 | 1/41 | 2/10 |
| 1600 | 8 | 41 | 1/8 | 1/37 | 2/5 |
| 1700 | 8 | 40 | 1/8 | 1/37 | 2/5 |
| 1800 | 8 | 40 | 1/8 | 1/37 | 2/5 |
| 1900 | 7 | 39 | 1/0 | 1/25 | 1/50 |
| 2000 | 7 | 35 | 1/0 | 1/25 | 1/50 |
| 2100 | 7 | 35 | 1/0 | 1/25 | 1/50 |
Note:
- Data provided by Eaton.
| Number of battery packs (P/N 40K9620) | |||||
|---|---|---|---|---|---|
| +0 | +1 | +2 | +3 | +4 | |
| Total Load (Watts) | Runtime ( hours / minutes) |
Runtime ( hours / minutes) |
Runtime ( hours / minutes) |
Runtime ( hours / minutes) |
Runtime ( hours / minutes) |
| 200 | 1/3 | 4/38 | 9/5 | 12/48 | 16/42 |
| 300 | 55 | 4/5 | 8/0 | 11/16 | 14/42 |
| 400 | 48 | 3/33 | 6/59 | 9/59 | 12/50 |
| 500 | 42 | 3/6 | 6/4 | 8/33 | 11/10 |
| 600 | 36 | 2/38 | 5/10 | 7/17 | 9/30 |
| 700 | 31 | 2/14 | 4/23 | 6/11 | 8/4 |
| 800 | 26 | 1/56 | 3/48 | 5/22 | 7/0 |
| 900 | 23 | 1/40 | 3/16 | 4/36 | 6/0 |
| 1000 | 19 | 1/23 | 2/44 | 3/51 | 5/2 |
| 1100 | 16 | 1/12 | 2/22 | 3/20 | 4/22 |
| 1200 | 14 | 1/3 | 2/4 | 2/54 | 3/48 |
| 1300 | 12 | 55 | 1/48 | 2/33 | 3/20 |
| 1400 | 10 | 47 | 1/32 | 2/10 | 2/50 |
| 1500 | 9 | 45 | 1/28 | 2/4 | 2/42 |
| 1600 | 9 | 41 | 1/20 | 1/53 | 2/28 |
| 1700 | 8 | 40 | 1/18 | 1/50 | 2/24 |
| 1800 | 8 | 40 | 1/18 | 1/50 | 2/24 |
| 1900 | 7 | 35 | 1/8 | 1/36 | 2/6 |
| 2000 | 7 | 35 | 1/8 | 1/36 | 2/6 |
| 2100 | 7 | 33 | 1/5 | 1/32 | 2/0 |
| 2200 | 6 | 30 | 58 | 1/22 | 1/48 |
| 2300 | 6 | 30 | 58 | 1/22 | 1/48 |
| 2400 | 6 | 30 | 58 | 1/22 | 1/48 |
| 2500 | 6 | 26 | 51 | 1/12 | 1/34 |
| 2600 | 5 | 25 | 49 | 1/9 | 1/30 |
| 2700 | 5 | 25 | 49 | 1/9 | 1/30 |
Note:
- Data provided by Eaton.
| Option number | Description |
|---|---|
| 40K9772 | 4.3m, 16A/208V, C19 to NEMA L6-20P (US) Line Cord |
| 40K9777 | 4.3m, 16A/220V, C19 to IRAM 2073 (Argentina) Line Cord |
| 40K9775* | 4.3m, 15A/125V, C19 to NBR 6147 (Brazil) Line Cord |
| 40K9766 | 4.3m, 16A/230V, C19 to CEE7-VII (Europe) Line Cord |
| 40K9769 | 4.3m, 16A/230V, C19 to IEC 309-P+N+G (Den/Sws) Line Cord |
| 40K9771 | 4.3m, 16A/230V, C19 to SI 32 (Israel) Line Cord |
| 40K9768 | 4.3m, 16A/230V, C19 to CEI 23-16 (Italy) Line Cord |
| 40K9770 | 4.3m, 16A/230V, C19 to SABS 164 (South Africa) Line Cord |
| 40K9767 | 4.3m, 13A/230V, C19 to BS 1363/A w/13A fuse (UK) Line Cord |
| 40K9773 | 4.3m, 15A/230V, C19 to AS/NZS 3112 (Aus/NZ) Line Cord |
| 40K9774 | 4.3m, 16A/220V, C19 to GB 2099.1 (China) Line Cord |
| 40K9776 | 4.3m, 16A/240V, C19 to IS 6538 (India) Line Cord |
* IBM has withdrawn this product from marketing.
IBM UPS 7500XHV, 10000XHV
| Tower or rack mount | |||||
|---|---|---|---|---|---|
| Version | UPS7500XHV | UPS10000XHV | UPS extend run battery pack | ||
| New T-M-F Ordering System6 | 2130RU1-1079 | 2130RU1-1080 | FC 5743 | ||
| Part number | 21303RX | 21304RX | 39Y8857 | ||
| (Old part number) | (21306RX) | (21308RX) | (25R5582) | ||
| UPS attributes | |||||
| Communication links to servers | Serial/USB/Enet | Serial/USB/Enet | -- | ||
| Color | black | black | black | ||
| EIA height | 6U | 6U | 3U | ||
| Versions | |||||
| 50 or 60Hz, single phase, VAC: | 220-240(xxx) 1, 2 | 220-240(xxx)1, 2 | - | ||
| Maximum power capacity (watts) | 6000 | 8000 | - | ||
| 10 Amp, IEC 320-C13 receptacles | - | - | - | ||
| 16 Amp, IEC 320-C19 receptacles | 43, 4 | 43, 4 | - | ||
| Line cord receptacle | terminal block5 | terminal block5 | - | ||
Notes:
- How-to-Read example for 200-240(208): Input VAC is 200-240
as
is the UPS output when electric service is active. When electric
service is interrupted and the UPS is on battery, the UPS output
is 208 VAC. - Battery output may be set to 208, 220, 225, 230 or 240 VAC.
- Four IEC power cables are provided to attach devices or PDUs
to the UPS outlet, which are 2m long with IEC 320-C19/C20
connectors. - Each outlet is protected by a 15amp circuit breaker.
- Requires electrician to connect directly to the terminal
block
inlet. - Type-Model-Feature ordering system now used in the US and
Canada.
| Number of battery packs (P/N 39Y8857) | ||||
|---|---|---|---|---|
| +0 | +1 | +2 | +4 | |
| Watts load | Runtime (hours/ minutes) |
Runtime (hours/ minutes) |
Runtime (hours/ minutes) |
Runtime (hours/ minutes) |
| 200 | 4/6 | 7/36 | 11/54 | 20/54 |
| 300 | 3/6 | 5/48 | 9/6 | 16/0 |
| 400 | 2/30 | 4/36 | 7/18 | 12/48 |
| 500 | 2/6 | 3/54 | 6/6 | 10/42 |
| 600 | 1/48 | 3/18 | 5/12 | 9/12 |
| 700 | 1/30 | 2/54 | 4/30 | 8/0 |
| 800 | 1/18 | 2/30 | 4/0 | 7/0 |
| 900 | 1/12 | 2/18 | 3/36 | 6/12 |
| 1000 | 1/6 | 2/0 | 3/12 | 5/42 |
| 1200 | 55 | 1/42 | 2/42 | 4/48 |
| 1400 | 47 | 1/30 | 2/18 | 4/6 |
| 1600 | 41 | 1/12 | 2/0 | 3/36 |
| 1800 | 36 | 1/6 | 1/48 | 3/12 |
| 2000 | 32 | 1/0 | 1/36 | 2/54 |
| 3000 | 19 | 39 | 1/0 | 1/48 |
| 4000 | 13 | 28 | 46 | 1/18 |
| 5000 | 10 | 21 | 35 | 1/0 |
| 6000 | 7 | 16 | 28 | 52 |
| 7000 | 5 | 13 | 23 | 44 |
| 8000 | 4 | 11 | 20 | 37 |
| Note: UPS7500 is rated for up to 6000 total watts; UPS10000 is rated for up to 8000 total watts. | ||||
Note:
- Data provided by APC.
IBM UPS5000HV
| Tower or rack mount | ||||
|---|---|---|---|---|
| Version | UPS5000HV | UPS extend run battery pack | ||
| New T-M-F Ordering System | 2419RU1-7618 | FC 5743 | ||
| Part Number | 24195KX | 39Y8857 | ||
| UPS attributes | ||||
| Communications links to servers | Serial/USB/Enet | - | ||
| Color | black | black | ||
| EIA height | 3U | 3U | ||
| Versions | ||||
| 50 or 60Hz, single phase,VAC: | 220-240(xxx) | - | ||
| Maximum power capacity (watts) | 4500 | - | ||
| 10-Amp, IEC 320-C13 (Device) receptacles | 8 | - | ||
| 16-Amp, IEC 320-C19 (PDU)receptacles | 2 | - | ||
| Receptacles (NEMA 5-15R) | - | - | ||
| Receptacles (NEMA L5-30R) | - | - | ||
| Attached line cord length, NEMA plug type | - | - | ||
| Line cord receptacle(IEC 320-) | - | - | ||
| Option number | Description |
|---|---|
| 40K9614 | 4.3m, 30A/208V, EPDU to NEMA L6-30P (US) Line Cord |
| 40K9612 | 4.3m, 32A/230V, EPDU to IEC 309 P+N+G (non-US) Line Cord |
| 40K9617 | 4.3m, 32A/230V, Souriau UTG Female to AS/NZ 3112 (Aus/NZ) Line Cord |
| 40K9618 | 4.3m, 32A/250V, Souriau UTG Female to KSC 8305 (S. Korea) Line Cord |
| Number of battery packs (P/N 39Y8857) | ||||
|---|---|---|---|---|
| +0 | +1 | +2 | +4 | |
| Watts load | Runtime (hours/ minutes) |
Runtime (hours/ minutes) |
Runtime (hours/ minutes) |
Runtime (hours/ minutes) |
| 50 | 6/49 | 18/3 | 31/32 | 59/56 |
| 100 | 4/50 | 12/51 | 22/29 | 42/46 |
| 200 | 3/0 | 8/3 | 14/6 | 26/50 |
| 300 | 2/9 | 5/47 | 10/10 | 19/22 |
| 400 | 1/39 | 4/30 | 7/54 | 15/04 |
| 500 | 1/20 | 3/39 | 6/26 | 12/17 |
| 600 | 1/07 | 3/04 | 5/24 | 10/20 |
| 700 | 57 | 2/38 | 4/39 | 8/54 |
| 800 | 50 | 2/18 | 4/04 | 7/48 |
| 900 | 44 | 2/02 | 3/37 | 6/56 |
| 1000 | 39 | 1/50 | 3/15 | 6/14 |
| 1200 | 32 | 1/30 | 2/41 | 5/11 |
| 1400 | 26 | 1/16 | 2/17 | 4/25 |
| 1600 | 22 | 1/6 | 1/59 | 3/50 |
| 1800 | 19 | 58 | 1/45 | 3/23 |
| 2000 | 17 | 52 | 1/33 | 3/1 |
| 2500 | 12 | 40 | 1/13 | 2/22 |
| 3000 | 9 | 32 | 1/0 | 1/57 |
| 3400 | 8 | 25 | 50 | 1/40 |
| 4000 | 6 | 23 | 43 | 1/25 |
| 4500 | 5 | 20 | 38 | 1/15 |
Note:
- Data provided by APC.
IBM 1500VA LCD 2U Rack UPS
| Tower or rack mount | ||||
|---|---|---|---|---|
| Version | UPS1500LV | UPS1500HV | ||
| New T-M-F Ordering System | 5395RU1-6656 | 5395RU1-6654 | ||
| Part Number | 53951AX | 53951KX | ||
| UPS attributes | ||||
| Communications links to servers | RS-232/USB | RS-232/USB | ||
| Color | black | black | ||
| EIA height | 2U | 2U | ||
| Versions | ||||
| 50 or 60Hz, single phase,VAC: | 100-120(xxx) | 230 | ||
| Maximum power capacity (watts) | 1000 | 1000 | ||
| 10-Amp, IEC 320-C13 receptacles | 2 | 4 | ||
| 16-Amp, IEC 320-C19 receptacles | - | - | ||
| 10-Amp, NEMA 5-15R receptacles | 4 | - | ||
| Attached line cord length, NEMA plug type | - | - | ||
| Line cord receptacle(IEC 320-) | One IEC 320-C13 to NEMA 5-15P |
- | ||
| +0 | ||
|---|---|---|
| Watts load | Percentage load | Internal Batteries |
| 250 | 25 | 14 |
| 500 | 50 | 11 |
| 750 | 75 | 7 |
| 1000 | 100 | 5 |
Note:
- Internal Batteries only
IBM 2200VA LCD 2U Rack UPS
| Tower or rack mount | |||||
|---|---|---|---|---|---|
| Version | UPS2200LV | UPS2200HV | UPS 2U Extended Battery Module | ||
| New T-M-F Ordering System | 5395RU2-6655 | 5395RU2-6656 | FC 5732 | ||
| Part Number | 53952AX | 53952KX | 46M4108 | ||
| UPS attributes | |||||
| Communications links to servers | RS-232/USB | RS-232/USB | - | ||
| Color | black | black | black | ||
| EIA height | 2U | 2U | 2U | ||
| Versions | |||||
| 50 or 60Hz, single phase,VAC: | 100-120(xxx) | 230 | 72 | ||
| Maximum power capacity (watts) | 1500/1920 | 1920 | - | ||
| 10-Amp, IEC 320-C13 receptacles | 2 | 8 | - | ||
| 16-Amp, IEC 320-C19 receptacles | 2 | 2 | - | ||
| 16-Amp, NEMA 5-20R receptacles | 6 | - | - | ||
| Attached line cord length, NEMA plug type | - | - | - | ||
| Line cord receptacle(IEC 320-) | One IEC 320-C19 to NEMA 5-20P |
- | - | ||
| Number of battery packs (P/N 46M4108) | |||
|---|---|---|---|
| +0 | +1 | ||
| Watts load | Percentage load | Internal Batteries |
Runtime (hours/ minutes) |
| 500 | 25 | 41 | 138 |
| 969 | 50 | 17 | 64 |
| 1450 | 75 | 10 | 40 |
| 1920 | 100 | 7 | 28 |
Note:
- One External Battery max
IBM 3000VA LCD 3U Rack UPS
| Tower or rack mount | ||||||
|---|---|---|---|---|---|---|
| Version | UPS3000LV | UPS3000HV | UPS3000HV | UPS 3U Extended Battery Module | ||
| New T-M-F Ordering System | 5395RU3-6657 | 5395RU3-6658 | 5395RU3-6659 | FC 5733 | ||
| Part Number | 53953AX | 53953JX | 53953KX | 69Y1982 | ||
| UPS attributes | ||||||
| Communications links to servers | RS-232/USB | RS-232/USB | RS-232/USB | - | ||
| Color | black | black | black | black | ||
| EIA height | 3U | 3U | 3U | 3U | ||
| Versions | ||||||
| 50 or 60Hz, single phase,VAC: | 100-120(xxx) | 208 | 230 | 96 | ||
| Maximum power capacity (watts) | 2300/2700 | 2700 | 2700 | - | ||
| 10-Amp, IEC 320-C13 receptacles | 2 | 2 | 8 | - | ||
| 16-Amp, IEC 320-C19 receptacles | 2 | 2 | 2 | - | ||
| 16-Amp, NEMA 5-20R receptacles | 2 | - | - | - | ||
| 16-Amp, NEMA L5-20R receptacles | 1 | - | - | - | ||
| 16-Amp, NEMA L6-20R receptacles | - | 2 | - | - | ||
| Attached line cord length, NEMA plug type | - | - | - | - | ||
| Line cord receptacle(IEC 320-) | One NEMA L5-30P length: 2.0m | One LP-73 to LS-37 | - | - | ||
| Number of battery packs (P/N 69Y1982) | |||
|---|---|---|---|
| +0 | +1 | ||
| Watts load | Percentage load | Internal Batteries |
Runtime (hours/ minutes) |
| 670 | 25 | 41 | 153 |
| 1340 | 50 | 16 | 62 |
| 2040 | 75 | 10 | 41 |
| 2700 | 100 | 6 | 27 |
Note:
- One External Battery max
IBM 6000VA LCD 4U Rack UPS
| Tower or rack mount | |||||
|---|---|---|---|---|---|
| Version | UPS6000HV | UPS6000HV | UPS 3U Extended Battery Module | ||
| New T-M-F Ordering System | 5395RU4-6660 | 5395RU4-6661 | FC 5734 | ||
| Part Number | 53956AX | 53956KX | 69Y1984 | ||
| UPS attributes | |||||
| Communications links to servers | RS-232/USB | RS-232/USB | - | ||
| Color | black | black | black | ||
| EIA height | 2U | 2U | 2U | ||
| Versions | |||||
| 50 or 60Hz, single phase,VAC: | 208 | 230 | 216 | ||
| Maximum power capacity (watts) | 5600 | 5600 | - | ||
| 10-Amp, IEC 320-C13 receptacles | - | 6 | - | ||
| 16-Amp, IEC 320-C19 receptacles | 4 | 4 | - | ||
| 16-Amp, NEMA L6-30R receptacles | 2 | - | - | ||
| Attached line cord length, NEMA plug type | - | - | - | ||
| Line cord receptacle(IEC 320-) | - | - | - | ||
| Number of battery packs (P/N 69Y1984) | |||
|---|---|---|---|
| +0 | +1 | ||
| Watts load | Percentage load | Internal Batteries |
Runtime (hours/ minutes) |
| 1400 | 25 | 51 | 112 |
| 2800 | 50 | 21 | 51 |
| 4200 | 75 | 12 | 31 |
| 5600 | 100 | 8 | 19 |
Note:
- One External Battery max
IBM 11000VA LCD 5U Rack UPS
| Tower or rack mount | ||||
|---|---|---|---|---|
| Version | UPS11000VA | UPS 3U Extended Battery Module | ||
| New T-M-F Ordering System | 5395RU5-6662 | FC 5735 | ||
| Part Number | 53959KX | 69Y1986 | ||
| UPS attributes | ||||
| Communications links to servers | RS-232/USB | RS-232/USB | ||
| Color | black | black | ||
| EIA height | 5U | 3U | ||
| Versions | ||||
| 50 or 60Hz, single phase,VAC: | 208 / 230 | 288 | ||
| Maximum power capacity (watts) | 10000 | - | ||
| 10-Amp, IEC 320-C13 receptacles | - | 4 | ||
| 16-Amp, IEC 320-C19 receptacles | 8 | - | ||
| 10-Amp, NEMA 5-15R receptacles | - | - | ||
| Attached line cord length, NEMA plug type | - | - | ||
| Line cord receptacle(IEC 320-) | Eight IEC 320 - C19 | - | ||
| Number of battery packs (P/N 69Y1986) | |||
|---|---|---|---|
| +0 | +1 | ||
| Watts load | Percentage load | Internal Batteries |
Runtime (hours/ minutes) |
| 2500 | 25 | 37 | 79 |
| 5000 | 50 | 14 | 35 |
| 7500 | 75 | 8 | 20 |
| 10000 | 100 | 5 | 14 |
Note:
- One External Battery max