Skip to main content




Appendix A. Uninterruptible power supplies


Attention
Attention:
A four-digit feature code is used to specify a component that is configurable in the IBM configurators, the eBusiness Configurator (eConfig) and the IBM Web-based Hardware Configurator, used in US and Canada. Options that do not have feature codes cannot be integrated by IBM into a system using these IBM configurators. To purchase options separately, refer to the option part number provided in this document.


UPS runtime estimator

Steps to determine UPS runtimes and suitable UPS for desired
configurations:

  1. Using the 'Power Product Data' table in the 'Power Data
    Overview Appendix', sum the power load (watts) of all devices
    in the configuration. Use either Maximum Load for minimum
    runtimes, or Typical Load for typical runtimes.
  2. Using the 'Runtimes' table, locate the configuration's total
    load calculated in step 1.
  3. Select the most appropriate UPS model to achieve the desired
    runtime.
Note: If the configuration's total load is greater than the entries in the
'Runtimes' table, split the load across two or more UPS units.


IBM UPS 750T, 1000T, 1500T

Table 1. IBM UPS750T, 1000T, 1500T attributes
  Tower
  Low Voltage Versions (US) UPS1000TLV UPS1500TLV
  New T-M-F Ordering System4 2130TU1-1083 2130TU1-1085
  Part Number 2130R3X 2130R5X
  (Old Part Number) (21303TX) (21305TX)
 
  Low Voltage Versions (Int'l) UPS1000THV UPS1500THV
  Part Number 2130R4X 2130R6X
  (Old Part Number) (21304TX) (21306TX)
 
  Japan Versions UPS1000TJV UPS1500TJV
  Part Number 2130R8X 2130R9X
  (Old Part Number) (21308TX) (21309TX)

UPS attributes

Communications links to servers

Serial/USB/Enet

Serial/USB/Enet

Color

black

black

APC SmartSlot

one

one

International models

50 or 60Hz, single phase,VAC:

220-240(xxx)1,2

220-240(xxx)1,2

10-Amp, IEC 320-C13 (Device)receptacles

8

8

16-Amp, IEC 320-C19 (PDU)receptacles

-

-

Receptacles (NEMA L5-20R)

-

-

Line cord length, NEMA plug

-

-

Line cord receptacle (IEC 320-)

C143

C143

Low Voltage Versions (US models and Japan models)

50 or 60Hz, single phase,VAC:

100-127(120)1

100-127(120)1

Receptacles (NEMA 5-15R)

8

8

Receptacles (NEMA L5-20R)

-

-

10-Amp, IEC 320-C13 (Device)receptacles

-

-

16-Amp, IEC 320-C19 (PDU)receptacles

-

-

Line cord length, NEMA plug

6ft, 5-15P

6ft, 5-15P

Line cord receptacle (IEC 320-)

-

-

Notes:
  1. How-to-Read example for 200-240(208): Input VAC is 200-240 as
    is the UPS output when electric service is active. When electric
    service is interrupted and the UPS is on battery, the UPS output
    is 208 VAC.
  2. Battery output may be set to 220, 225, 230 or 240 VAC.
  3. Country-specific line cords available as options.
  4. Type-Model-Feature ordering system now used in the US and Canada.

Table 2. IBM UPS700T, 1000T, 1500T Runtimes1
  Tower
  UPS750T UPS1000T UPS1500T
Total load (watts) Runtime (minutes) Runtime (minutes) Runtime (minutes)
50 105 224 269
100 57 127 157
200 28 64 80
300 18 41 51
400 13 29 37
500 10 23 28
600 - 18 22
700 - 15 18
800 - 12 15
900 - 11 13
1000 - 9 11
1200 - - 9
1400 - - 7
Notes:
  1. Data provided by APC.

Table 3. Country-specific line cords usable with UPS750THV, UPS1000THV, and UPS1500THV:
Option number Description
39Y7930 2.8m, 10A/220V, C13 to IRAM 2073 (Argentina) Line Cord
39Y7929 2.8m, 10A/125V, C13 to NBR 6147 (Brazil) Line Cord
39Y7917 2.8m, 10A/230V, C13 to CEE7-VII (Europe) Line Cord
39Y7918 2.8m, 10A/230V, C13 to DK2-5a (Denmark) Line Cord
39Y7920 2.8m, 10A/230V, C13 to SI 32 (Israel) Line Cord
39Y7921 2.8m, 10A/230V, C13 to CEI 23-16 (Italy) Line Cord
39Y7922 2.8m, 10A/230V, C13 to SABS 164 (South Africa) Line Cord
39Y7919 2.8m, 10A/230V, C13 to SEV 1011-S24507 (Sws) Line Cord
39Y7923 2.8m, 10A/230V, C13 to BS 1363/A (UK) Line Cord
39Y7924 2.8m, 10A/230V, C13 to AS/NZS 3112 (Aus/NZ) Line Cord
39Y7927 2.8m, 10A/240V, C13 to IS6538 (India) Line Cord
39Y7928 2.8m, 10A/220V, C13 to GB 2099.1 (China) Line Cord
39Y7925 2.8m, 10A/220V, C13 to KSC 8305 (S. Korea) Line Cord

IBM UPS3000LV and HV

Table 4. IBM UPS3000LV and HV Attributes
  Tower or rack mount
  Version UPS3000LV UPS3000HV UPS extend run battery pack
  New T-M-F Ordering System1 2130RU1-1077 2130RU1-1078 FC 5742
  Part Number 21301RX 21302RX 40K9620

UPS attributes

Communications links to servers

Serial/USB/Enet

Serial/USB/Enet

-

Color

black

black

black

EIA height

2U

2U

2U

Versions

 

Low Voltage

High Voltage

 

50 or 60Hz, single phase,VAC:

120(120)1

220-240(xxx)1, 2

-

Maximum power capacity (watts) 2700 2700 -

10-Amp, IEC 320-C13 (Device) receptacles

-

94

-

16-Amp, IEC 320-C19 (PDU)receptacles

-

13

-

Receptacles (NEMA 5-15R)

6

-

-

Receptacles (NEMA L5-30R)

1

-

-

Attached line cord length, NEMA plug type

12ft, L5-30P

-

-

Line cord receptacle(IEC 320-)

-

C205

-

Notes:
  1. How-to-Read example for 200-240(208): Input VAC is 200-240 as
    is the UPS output when electric service is active. When electric
    service is interrupted and the UPS is on battery, the UPS output
    is 208 VAC.
  2. Battery output may be set to 220, 225, 230 or 240 VAC.
  3. One 2.5m PDU jumper cable ships with the UPS for attachment
    from the IEC 320-C19 receptacle to a Power Distribution Unit (PDU)
    with C20 inlet.
  4. Four IEC power cables are provided to attach devices to the
    UPS outlets, which are 2m long with IEC 320-C13/C14 connectors.
  5. Country-specific line cords are available as options.
  6. Type-Model-Feature ordering system now used in the US and Canada.

Table 5. IBM UPS3000LV Runtimes1
  Number of battery packs (P/N 40K9620)
  +0 +1 +2 +3 +4
Total Load (Watts) Runtime
( hours / minutes)
Runtime
( hours / minutes)
Runtime
( hours / minutes)
Runtime
( hours / minutes)
Runtime
( hours / minutes)

200

1/3

5/16

7/57

11/15

14/34

300

55

4/35

7/0

9/55

12/50

400

48

4/1

6/6

8/39

11/12

500

42

3/31

5/19

7/31

9/44

600

36

3/3

4/31

6/24

8/17

700

31

2/35

3/50

5/26

7/2

800

26

2/12

3/20

4/43

6/6

900

23

1/55

2/51

4/2

5/14

1000

19

1/38

2/23

3/23

4/23

1100

16

1/22

2/4

2/56

3/48

1200

14

1/11

1/48

2/33

3/19

1300

12

1/2

1/35

2/14

2/54

1400

10

54

1/20

1/54

2/28

1500

9

46

1/11

1/41

2/10

1600

8

41

1/8

1/37

2/5

1700

8

40

1/8

1/37

2/5

1800

8

40

1/8

1/37

2/5

1900

7

39

1/0

1/25

1/50

2000

7

35

1/0

1/25

1/50

2100

7

35

1/0

1/25

1/50

Notes:
  1. Data provided by Eaton.

Table 6. IBM UPS3000HV Runtimes1
  Number of battery packs (P/N 40K9620)
  +0 +1 +2 +3 +4
Total Load (Watts) Runtime
( hours / minutes)
Runtime
( hours / minutes)
Runtime
( hours / minutes)
Runtime
( hours / minutes)
Runtime
( hours / minutes)

200

1/3

4/38

9/5

12/48

16/42

300

55

4/5

8/0

11/16

14/42

400

48

3/33

6/59

9/59

12/50

500

42

3/6

6/4

8/33

11/10

600

36

2/38

5/10

7/17

9/30

700

31

2/14

4/23

6/11

8/4

800

26

1/56

3/48

5/22

7/0

900

23

1/40

3/16

4/36

6/0

1000

19

1/23

2/44

3/51

5/2

1100

16

1/12

2/22

3/20

4/22

1200

14

1/3

2/4

2/54

3/48

1300

12

55

1/48

2/33

3/20

1400

10

47

1/32

2/10

2/50

1500

9

45

1/28

2/4

2/42

1600

9

41

1/20

1/53

2/28

1700

8

40

1/18

1/50

2/24

1800

8

40

1/18

1/50

2/24

1900

7

35

1/8

1/36

2/6

2000

7

35

1/8

1/36

2/6

2100

7

33

1/5

1/32

2/0

2200

6

30

58

1/22

1/48

2300

6

30

58

1/22

1/48

2400

6

30

58

1/22

1/48

2500

6

26

51

1/12

1/34

2600

5

25

49

1/9

1/30

2700

5

25

49

1/9

1/30

Notes:
  1. Data provided by Eaton.


Table 7. Country-specific line cords usable with UPS3000HV
Option number Description
40K9772 4.3m, 16A/208V, C19 to NEMA L6-20P (US) Line Cord
40K9777 4.3m, 16A/220V, C19 to IRAM 2073 (Argentina) Line Cord
40K9775 4.3m, 15A/125V, C19 to NBR 6147 (Brazil) Line Cord
40K9766 4.3m, 16A/230V, C19 to CEE7-VII (Europe) Line Cord
40K9769 4.3m, 16A/230V, C19 to IEC 309-P+N+G (Den/Sws) Line Cord
40K9771 4.3m, 16A/230V, C19 to SI 32 (Israel) Line Cord
40K9768 4.3m, 16A/230V, C19 to CEI 23-16 (Italy) Line Cord
40K9770 4.3m, 16A/230V, C19 to SABS 164 (South Africa) Line Cord
40K9767 4.3m, 13A/230V, C19 to BS 1363/A w/13A fuse (UK) Line Cord
40K9773 4.3m, 15A/230V, C19 to AS/NZS 3112 (Aus/NZ) Line Cord
40K9774 4.3m, 16A/220V, C19 to GB 2099.1 (China) Line Cord
40K9776 4.3m, 16A/240V, C19 to IS 6538 (India) Line Cord

IBM UPS 7500XHV, 10000XHV

Table 8. IBM UPS7500XHV, 10000XHV attributes
    Tower or rack mount
  Version UPS7500XHV UPS10000XHV UPS extend run battery pack
  New T-M-F Ordering System6 2130RU1-1079 2130RU1-1080 FC 5743
  Part number 21303RX 21304RX 39Y8857
  (Old part number) (21306RX) (21308RX) (25R5582)
UPS attributes        
Communication links to servers Serial/USB/Enet Serial/USB/Enet --
Color black black black
EIA height 6U 6U 3U
Versions        
50 or 60Hz, single phase, VAC: 220-240(xxx) 1, 2 220-240(xxx)1, 2 -
Maximum power capacity (watts) 6000 8000 -
10 Amp, IEC 320-C13 receptacles - - -
16 Amp, IEC 320-C19 receptacles 43, 4 43, 4 -
Line cord receptacle terminal block5 terminal block5 -
Notes:
  1. How-to-Read example for 200-240(208): Input VAC is 200-240 as
    is the UPS output when electric service is active. When electric
    service is interrupted and the UPS is on battery, the UPS output
    is 208 VAC.
  2. Battery output may be set to 208, 220, 225, 230 or 240 VAC.
  3. Four IEC power cables are provided to attach devices or PDUs
    to the UPS outlet, which are 2m long with IEC 320-C19/C20
    connectors.
  4. Each outlet is protected by a 15amp circuit breaker.
  5. Requires electrician to connect directly to the terminal block
    inlet.
  6. Type-Model-Feature ordering system now used in the US and
    Canada.

Table 9. IBM UPS7500XHV, 10000XHV Runtimes1
  Number of battery packs (P/N 39Y8857)
  +0 +1 +2 +4
Watts load Runtime
(hours/
minutes)
Runtime
(hours/
minutes)
Runtime
(hours/
minutes)
Runtime
(hours/
minutes)
200 4/6 7/36 11/54 20/54
300 3/6 5/48 9/6 16/0
400 2/30 4/36 7/18 12/48
500 2/6 3/54 6/6 10/42
600 1/48 3/18 5/12 9/12
700 1/30 2/54 4/30 8/0
800 1/18 2/30 4/0 7/0
900 1/12 2/18 3/36 6/12
1000 1/6 2/0 3/12 5/42
1200 55 1/42 2/42 4/48
1400 47 1/30 2/18 4/6
1600 41 1/12 2/0 3/36
1800 36 1/6 1/48 3/12
2000 32 1/0 1/36 2/54
3000 19 39 1/0 1/48
4000 13 28 46 1/18
5000 10 21 35 1/0
6000 7 16 28 52
7000 5 13 23 44
8000 4 11 20 37
Note: UPS7500 is rated for up to 6000 total watts; UPS10000 is rated for up to 8000 total watts.
Notes:
  1. Data provided by APC.

November 17, 2009