IBM 1000 VA LCD Tower UPS

IBM  1000 VA LCD Tower UPS technical specifications
 
IBM model LCD Tower UPS (100 V) LCD Tower UPS (120 V) LCD Tower UPS (230 V)
IBM part number 53961JX 53961AX 53961KX
VA/Watts Rating 1000 VA/750 W
 
1000 VA/750 W 1000 VA/750 W
Nominal Output Voltage (Vac) 100 V 120 V 230 V
Waveform type Sine wave
Output connections (All output receptacles are controllable via Two Load Groups (segments)) (8) NEMA 5-15R
 
(8) NEMA 5-15R (8) IEC 320 C13
Input
Nominal input voltage 100 V
 
120 V 230 V
 
Input frequency (auto sensing) 50/60 Hz +/- 3 Hz
Maximum input current 12 amps 12 amps 10 amps
Input Connection Type IEC 320 C14
Input cords IEC 320 C13 to JIS C-8303 2.8m
 
IEC 320 C13 to NEMA 5-15P 2.8m Optional country-specific line cords
Input voltage range, mains operations 84 - 121 V for 100 V
 
97 - 145 V 160 - 286 V
Batteries
Typical backup times 15 minutes (@ 50% load)
6 minutes (@ full load)
Battery type Valve Regulated Lead Acid (VRLA)—Maintenance-free, sealed, leak-proof
Optional External Battery Pack N/A
Typical recharge time 4 hours to 90% charge from a UPS/battery discharge of 50% rated load
Communications and Management
Interface port USB HID Port/ Serial/Optional LAN Card
Management software included IBM UPS Manager software
Control panel Intelligent three-button, backlit graphical LCD displays vital UPS status in nine languages
Audible alarm Alarm when on battery: distinctive low-battery alarm
Remote Power Off (REPO) REPO port
Surge Protection and Filtering
Surge energy rating 1200 joules 1200 joules 2400 joules
Filtering ANSI/IEEE C62.41; 1991 CATEGORYB3 (SURGE)
Physical
Height 246 mm/9.7 in.
Width 160 mm/6.3 in.
Depth 436 mm/17.2 in.
Weight 14 kg/32 lb
Color IBM black bezel
Environmental and Safety
Audible noise, 1 meter from unit surface Normal operation at rated load and Battery Discharge Mode <55 dbA
For load <70% <50 dbA
Efficiency 95% minimum at full rated load—normal usage, not during battery recharge
Operating temperature 0°C to 40°C (32°F to 104°F)
Relative humidity 0 to 95% non-condensing
Safety Markings UL, cUL; IEC/EN 62040-1-1; IEC/EN 60950-1 with TUV GS, TUV CB Reprot, CE Mark, TUV CB Report transfer global
EMC Markings 100 V/120 V: FCC Class B, EN44022 Class A; BSMI, CNS14757-2, Class A
230 V: CE (per IEC/EN62040-2: Emissions, Category C1; Immunity, Category C2); VCCI, Class A; C-Tick, AS/NZS 3548, Class A; IEC61000-3-11: 2000; IEC61000-3-12: 2004; ICES (BSMI); ICES Canada
IBM 1000 VA LCD Tower options at a glance
Network Management Card (NMC)
Part number 46M4110
Environmental Monitoring Probe
Part number 46M4113
IBM 1000 VA LCD Tower UPS run time chart*
Load Run time in minutes, using
Percent Load VA Watts standard internal batteries
25% 250 188 25
50% 500 375 15
75% 750 573 7
100% 1000 750 6

Contact IBM

 

Browse System x